Menu

Connect with us

CSTKC10KS10KVA8KWUPS power supply host 1 12V38AH batteries, 16 with battery box

UPS host, battery, battery box matching; 10KVA delay for half an hour

price:USD$8390.00
discount 70% in 2018-10-14 to 2018-10-16
price: USD$ 5873.00
freight :USD$18.00,(Express)
freight :USD$7.00,(Postal parcel)
views:0
Search Similar or mail to saler or send message to saler

Pay with PayPal, PayPal Credit or any major credit card

Purchase notes:This product defaults to hairGeneral LogisticsNote: logistics to the city after the arrival of the need to mention, such as the need for delivery, plus delivery fee.

CSTKC10KS (10000VA8000W) on-line switching time of sine wave output with a voltage stabilizing function UPS uninterruptible power supply host 1 external 16 CSTK12V38AH VRLA battery box 1

Non human factors damage a full set of three years warranty!     

 

main features:

True conversion over the line technology

Full digital control of DSP technology, high reliability

The input power factor correction of more than 0.99 active

The output power factor is 0.8

Wide input voltage range

50hz/60hz frequency converter mode

Output voltage: 208/220/230/240VAC

LCD and LED user interface

Short circuit, overload and over temperature protection

Both sides: automatically restart after public power supply

Because the battery is low, the UPS is closed

Optimized design of an intensity scalable rechargeable battery

performance

Generator compatibility

Smart RS232 Communications

Optional emergency shutdown function (EPO)

Optional maintenance bypass available

Optional SNMP card slot

Optional N+X parallel redundancy

Small size, particularly suitable for finance, telecommunications, Trasffic, government, industry and education.

 

Product specification
Machine model
C6K
C6KS
C10K
C10KS
3C10KS
3C15KS
3C20KS
Size (width, depth, height, height) mm
248×500×616
240×500×460
248×500×616
240×500×460
248×500×616
Net weight (Kg)
57
18
67.5
20
27
35
35
power
Apparent power (KVA)
6KVA
6KVA
10KVA
10KVA
10KVA
15KVA
20KVA
Active power (KW)
4.8KW
4.8KW
8KW
8KW
8KW
12KW
16KW
AC input
Input mode
Single phase grounding
Voltage range
120VAC~275VAC±5V
Bypass voltage
80VAC×(1±5%)~285VAC(1±5%)
Current *
33A.max
37A.max
55A.max
59A.max
86A.max
112A.max
frequency range
46Hz~54Hz
power factor
0.99
0.95
output
Output mode
Single phase grounding, three-phase four wire + ground wire
Voltage
220VAC* (1 + 1%) inverter output
Electric current
27A
45A
68A
91A
frequency
46HzTo 54Hz (city power mode, followed by city power), 50Hz * (1 + 0.1%) (battery mode)
power factor
0.8
Overload capacity
105%To 125%, 1 minutes after the bypass; 125% to 150%, 30 seconds after the bypass, 1 minutes after the broken output; >150%, 0.5 after bypass
Peak factor
3:1
Distortion degree
THD<2%(Linear load
Battery (battery used at high temperature, life will decline sharply)
Battery voltage
Standard 192VDC (customized for 240V)
Battery capacity x quantity
12VDCX 16 section (can be customized for 20 sections)
Backup time
4Minutes (full load)
Depends on the capacity of the external battery
3Minutes (full load)
Depends on the capacity of the external battery
Charging time
7Hours charge up to 90%
Depends on the capacity of the external battery
7Hours charge up to 90%
Depends on the capacity of the external battery
Communication and monitoring function
RS232(can turn 485), dry nodes, smart slot (scalable SNMP, SMS and other monitoring methods)
 
 
 
 
 
 
 
 
*.The maximum current is UPS input 187V, the output is full load, the charger is under full load working condition.
 
 
 
Note: the product should be in kind. Product design, technical specifications updated without notice.